What size wire do I need?

Enter the load, conductor metal, and termination temperature to get the minimum wire size from the NEC 310.16 ampacity table.

A

Amps the circuit carries.

Minimum wire size

8 AWG

copper at 75°C

50A

ampacity of that size

40A

required (with 125% if cont.)

6 AWG

next size up

NEC 310.16, 30°C ambient, ≤3 conductors. Derate for conduit fill, higher ambient, or long runs — and check the 15/20/30A breaker limit on 14/12/10 AWG (240.4(D)).

Long run? Also check voltage drop. Then price the wire, breakers, and labor into a free estimate.

Recibe la próxima herramienta antes que nadie

Nuevas calculadoras gratuitas y un consejo corto por semana para llevar un negocio de oficios: sin spam, te das de baja cuando quieras.

Cómo se calcula

The calculator picks the smallest conductor whose allowable ampacity (NEC 310.16, at your temperature column) is at least the load — sized to 125% if you mark it continuous.

Base ampacities assume 30°C ambient and three or fewer current-carrying conductors. Real installs derate for conduit fill, ambient heat, and bundling, must respect the weakest termination’s temperature rating (110.14(C)), and cap 14/12/10 AWG at 15/20/30A breakers (240.4(D)). Use this to get in the ballpark, then verify against the full install conditions.

Es una estimación de planeación: conviene confirmarla siempre con la normativa, las especificaciones y tu proveedor antes de pedir o instalar.

Wire Size Calculator: FAQ

What size wire do I need for my amps?

Match the load to the conductor ampacity in the NEC 310.16 table for your metal and termination temperature. At the common 75°C column, copper handles 20A on 12 AWG, 30A on 10 AWG, 50A on 8 AWG, 65A on 6 AWG, and 100A on 3 AWG. This calculator picks the smallest size that carries your load.

What is the difference between the 60, 75, and 90°C columns?

They are the conductor’s insulation temperature ratings. You must size to the temperature rating of the weakest termination — most breakers and lugs are rated 75°C, so the 75°C column is the usual choice even with 90°C wire.

Why does a continuous load need bigger wire?

For a load running 3 hours or more, the NEC requires the conductor and breaker to be sized at 125% of the load. A 40A continuous load is sized as 50A. Toggle "continuous" and the calculator applies the 125%.

Do I still need to derate?

Often, yes. These are base ampacities at 30°C with three or fewer conductors. More conductors in a conduit, higher ambient temperature, or bundling require derating to a smaller allowable ampacity — and 14, 12, and 10 AWG have breaker limits of 15, 20, and 30A regardless (NEC 240.4(D)).