Work out the airflow three different ways

Airflow a room needs from its volume and air changes, airflow a system should move at CFM per ton, or airflow through a round or rectangular duct at a measured velocity.

ft
ft
ft

2,240 ft³ at 6 air changes per hour

224

CFM

2,240

room volume (ft³)

6

air changes per hour

0.56

tons at 400 CFM/ton

381

equivalent m³/h

CFM = room volume × ACH ÷ 60. Air changes per hour is a ventilation rule of thumb, not a load calculation — for equipment sizing the load comes first and the airflow follows it.

Get the next tool first

New free calculators and one short weekly tip for running a trades business — no spam, unsubscribe anytime.

How this is calculated

Room: CFM = length × width × height × ACH ÷ 60. Air changes per hour is a ventilation target, not a load result.

Per ton: CFM = tons × CFM per ton, with 400 the standard design point — around 350 in humid climates for better moisture removal, 450 in dry ones. One ton is 12,000 BTU/h.

Duct: CFM = area in square feet × velocity in feet per minute. Round duct area is π × radius², rectangular is width × height, and both come back in square inches — divide by 144.

Design arithmetic, not a substitute for a load calculation. Equipment selection follows a proper Manual J, and duct design a Manual D; this gives you the airflow figures that sit alongside them.

This is a planning estimate — always confirm against code, spec, and your supplier before ordering or installing.

CFM Calculator: FAQ

How do you calculate CFM for a room?

Multiply length by width by height to get the volume in cubic feet, multiply by the air changes per hour you are targeting, then divide by 60 to get cubic feet per minute. A 20 by 14 room with an 8 ft ceiling is 2,240 cubic feet, so at 6 air changes an hour it needs 224 CFM.

What is CFM per ton?

The airflow a cooling system should move for each ton of capacity, and 400 CFM per ton is the standard design point. Dry climates often run closer to 450 to move more air, and humid climates closer to 350 so the coil has longer to pull moisture out of the air. One ton is 12,000 BTU/h.

How do you calculate CFM in a duct?

Duct area in square feet multiplied by air velocity in feet per minute. An 8 inch round duct is 50.3 square inches, which is 0.349 square feet, so at 700 FPM it carries about 244 CFM. Divide the area in square inches by 144 to get square feet — forgetting that step is the usual mistake.

What are air changes per hour?

How many times the entire volume of air in a space is replaced each hour. Living spaces are typically designed around 4 to 6, kitchens nearer 8, bathrooms 10, and workshops or paint booths 15 to 20. It is a ventilation rule of thumb rather than a load calculation.

What velocity should ducts be designed at?

For residential work, trunk lines are usually designed around 700 to 900 FPM and branches around 600 to 700. Going faster moves more air through the same duct but noise rises sharply with velocity, so a system pushed too hard tends to become audible before it becomes efficient.

Is CFM the same as air conditioner sizing?

No — they answer different questions and depend on each other. Sizing tells you the capacity in BTU or tons the space needs, and airflow is what that capacity requires to actually deliver it. Size first from the load, then work out the CFM. Our HVAC load calculator handles the capacity side.